Maryland Journeyman Electrician Practice Test - Full-Length Test 1

A full-length, 66-question practice exam covering all 8 core NEC topic areas, weighted the same way the real exam is. Modeled on Maryland's real licensing exam format. Premium — part of Full-Length Pro.

See Maryland electrician licensing requirements, fees & exam format

TOPICS COVERED
Welders Equipment Installation NEC Practice Tests Services Boxes

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 240 min for 66 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account required. All questions include detailed explanations and NEC references.

Most state Journeyman exams have 80–100 questions covering NEC code, wiring methods, branch circuits, motor controls, and load calculations.

Most states require a 70–75% passing score. This practice test uses the same 70% pass threshold so you know where you stand.

Questions are written to the 2023 NEC. Check your state licensing board to confirm which edition your state has adopted.

How to Use This Practice Test

This Maryland Journeyman Electrician Practice Test - Full-Length Test 1 has 66 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: This is an open-book exam — tab your NEC index and Articles 210, 250, and 430 before you start.

  • Topics covered: Branch circuits, grounding, wiring methods, load calculations, and motors.
  • Passing score: 70–75% (most states). Aim for 80% on practice tests so the real exam feels easy.
  • Questions: 66 multiple-choice, one correct answer each
FULL-LENGTH PRO EXAM
66
Questions
240 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

About This Exam

Sized and paced to match a real state licensing exam (Maryland). Finish it to get a free category-by-category score report.


Go Pro
  • Up to 15 Maryland exam variants
  • Detailed topic report every time
  • Personalized study guides & Study Coach

One-time payment — $19.00, lifetime access

See Pro Plans
JOURNEYMAN · NEC 2023
Maryland Journeyman Electrician Practice Test - Full-Length Test 1
Q1 / 66
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Maryland Journeyman Electrician Practice Test - Full-Length Test 1 — Question List

Question 1: A nonautomatic arc welder has a 60% duty cycle and primary current of 50A. Table 630.11(A) gives a multiplier of 0.78 for 60% duty cycle. What is the minimum branch circuit conductor ampacity?

  • 33A — using a 0.65 factor
  • 39A — 50A × 0.78
  • 44A — 50A × 0.89 (80% factor)
  • 50A — no duty cycle reduction

NEC Reference: NEC 630.11(A)

Question 2: An electrician installs a motor according to all NEC rules, but the motor manufacturer instructions say to use a specific wiring method and conductor size that is more restrictive than what the NEC requires. Which takes precedence?

  • The NEC always overrides manufacturer instructions
  • The manufacturer installation instructions — they are part of the listing
  • Whichever is less expensive to install
  • The local building code, which supersedes both

NEC Reference: NEC 110.3(B)

Question 3: What shall be the maximum weight of the lightening fixture when it is supported only by the screw shell of the lamp holder?

  • 4 pounds
  • 6 pounds
  • 8 pounds
  • 10 pounds

NEC Reference: NEC 410.30(A)

Question 4: What is ampacity of 1/0 THWN conductor in a dry location at an ambient temperature of 1040 F if the raceway contains four 1/0 THWN conductors?

  • 132
  • 124
  • 165
  • 170

NEC Reference: NEC 310.15(B)(16)

Question 5: A single family dwelling unit has a connected load of 4000 VA. which of the following is the calculated demand load?

  • 3350 VA
  • 3550 VA
  • 4000 VA
  • 3850 VA

NEC Reference: NEC 220.42

Question 6: Which of the following is the ampacity of 4 AWG SE cable?

  • 70 A
  • 65 A
  • 80 A
  • 85 A

NEC Reference: NEC 338.10(B)

Question 7: What is the minimum feeder or service load for cloth dryers in a dwelling unit?

  • 5000 watts
  • 2800 watts
  • 4500 watts
  • 6500 watts

NEC Reference: NEC 220.54

Question 8: How many types of 4 wire feeders shall be permitted to utilize a common neutral?

  • 2
  • 3
  • 4
  • 5

NEC Reference: NEC 215.4

Question 9: How many maximum number of receptacles are permitted on — a 20 ampere breaker supplied by 120 volts power source in a shopping complex?

  • 13
  • 10
  • 18
  • 11

NEC Reference: NEC 220.14(I)

Question 10: The allowable ampacity of the branch circuit conductors shall be permitted to be not less than the sum of the continuous load plus ......................... load

  • non-continuous load
  • rated load
  • Maximum load

NEC Reference: NEC 210.19

Question 11: What are the maximum allowable service dis connectors consist for each service?

  • 4
  • 2
  • 6
  • 8

NEC Reference: NEC 230.71(A)

Question 12: Which of the following circuits shall not be connected to system containing trolley wires?

  • Circuits for lightening
  • Grounding wires
  • Ungrounded trolley wires
  • Bonding wires

NEC Reference: NEC 110.19

Question 13: Per 230.95, ground-fault protection of equipment is required on solidly grounded wye services of more than 150V to ground rated:

  • 400A or more
  • 600A or more
  • 1000A or more
  • 2000A or more

NEC Reference: NEC 230.95

Question 14: Which of the following is the maximum rating of a branch circuit that supply the primary of low voltage lighting system power supply?

  • 20 amperes
  • 25 amperes
  • 15 amperes
  • 30 amperes

NEC Reference: NEC 411.6

Question 15: A device box is mounted in a concrete block wall. How far can the front edge of the box be set back from the finished wall surface?

  • No setback allowed — the box must be flush
  • — inch maximum setback
  • — inch maximum setback
  • 1 inch maximum setback

NEC Reference: NEC 314.20

Question 16: Show window load per 220.43(A) is calculated at not less than:

  • 50 VA per linear foot
  • 100 VA per linear foot
  • 180 VA per linear foot
  • 200 VA per linear foot

NEC Reference: NEC 220.43(A)

Question 17: A motor is in the basement and its disconnect is on the first floor where you cannot see the motor. What does the NEC allow in this situation?

  • A second disconnect must be installed at the motor
  • The disconnect must be capable of being locked in the open position
  • A warning label on the motor is sufficient
  • Nothing extra is needed as long as the disconnect is identified

NEC Reference: NEC 430.102(B)

Question 18: For a 300 ampere electrical circuit, what is the minimum size copper equipment grounding conductor as per NEC?

  • 6 AWG
  • 4 AWG
  • 8 AWG
  • 10 AWG

NEC Reference: NEC 250.122

Question 19: What is the minimum feeder/service conductor calculated load for an electrical sign?

  • 15000 VA
  • 12000 VA
  • 18000 VA
  • 10000 VA

NEC Reference: NEC 220.14(F)

Question 20: How many number of entrances should be provided to give access from working space about electrical equipment?

  • 1
  • 2
  • 3
  • 4

NEC Reference: NEC 110.26

Question 21: A metal underground water pipe is used as a grounding electrode. What additional requirement must be met?

  • The pipe must be at least 10 feet long in contact with the earth
  • At least one supplemental electrode must also be installed
  • The pipe must be bonded to every metallic water fixture in the building
  • The water company must be notified before using the pipe as an electrode

NEC Reference: NEC 250.53(D)(2)

Question 22: Per 220.61(C)(2), the feeder neutral load for non-linear (electric-discharge or harmonic-producing) loads is calculated at:

  • 70% of the load above 200A
  • 100% — no reduction permitted
  • 50% of the total
  • 125% of the load

NEC Reference: NEC 220.61(C)(2)

Question 23: The minimum headroom of the working space in front of a panelboard, switchboard, or motor control center must be at least:

  • 6 feet
  • 6.5 feet (2.0 m)
  • 7 feet
  • 8 feet

NEC Reference: NEC 110.26(A)(3)

Question 24: For a permanently installed swimming pool at a house, receptacles that are located between 6 feet and 20 feet from the pool edge must have:

  • AFCI protection
  • GFCI protection
  • Tamper-resistant protection only
  • No special protection — the 6-foot rule is all that applies

NEC Reference: NEC 680.22(A)

Question 25: Which of the following is the minimum size of fixture size that can use for wiring control circuits?

  • 18 AWG
  • 16 AWG
  • 10 AWG
  • 12 AWG

NEC Reference: NEC 402.6

Question 26: Without applying any de-rating factor for conductor current carrying capacity, how many conductors can run parallel in raceway or cable?

  • 4
  • 3
  • 5
  • 6

NEC Reference: NEC 310.15(B)(3)(a)

Question 27: In which of the following the panel boards must be enclosed?

  • Cut boxes
  • Cabinets
  • All options are correct
  • Enclosures designed for the purpose

NEC Reference: NEC 408.38

Question 28: A cable clamp inside a device box counts for how many conductor volumes in the box fill calculation?

  • Zero — clamps are part of the box hardware and are ignored
  • One conductor volume for all clamps combined
  • One conductor volume per clamp
  • Two conductor volumes regardless of clamp size

NEC Reference: NEC 314.16(B)(2)

Question 29: A 4800 watts electric motor is connected to 240 volts single phase supply, 2 wire circuit. what is the minimum size THW conductor that is required to supply the load?

  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG

NEC Reference: NEC 424.3(B)

Question 30: A 277/480V, 3-phase, 4-wire wye service in a commercial building is rated at 2000A. Per 230.95, does this service require ground-fault protection of equipment (GFP)?

  • No — GFP is only required on services above 2500A
  • Yes — voltage to ground exceeds 150V and the service rating is 1000A or more
  • No — 277/480V systems are exempt from the GFP requirement
  • Yes — GFP is required on all commercial services regardless of voltage

NEC Reference: NEC 230.95

Question 31: What is the corrected ampacity of a 2/0 THWN conductor in a dry location, If the ambient temperature of the location is 450 C?

  • 170 Amperes
  • 188 Amperes
  • 139 Amperes
  • 160 Amperes

NEC Reference: NEC 310.15(B)(16)

Question 32: Mutli-wire branch circuits shall not be permitted in class I division I locations.

  • True
  • False

NEC Reference: NEC 501.40

Question 33: A motor nameplate shows FLA = 40A and service factor = 1.15. What is the highest trip setting allowed on the overload relay?

  • 40A — match the FLA exactly
  • 46A × 115% of FLA
  • 50A × 125% of FLA
  • 56A × 140% of FLA

NEC Reference: NEC 430.32(A)(1)

Question 34: For a 400A service with 600 kcmil copper conductors, what is the minimum GEC size per Table 250.66?

  • 1/0 AWG copper
  • 4 AWG copper
  • 2 AWG copper
  • 3/0 AWG copper

NEC Reference: NEC Table 250.66

Question 35: When one or more equipment grounding conductors or equipment bonding jumpers enters in a metal box can be considered as how many number of total conductors in a metal box?

  • single conductor
  • double conductor
  • half of the number of conductors

NEC Reference: NEC 314.16(5)

Question 36: What is the minimum size of THWN conductors required for single phase 10 HP motor — connected to 240 volts supply?

  • 4 AWG THWN Copper
  • 6 AWG THWN Copper
  • 8 AWG THWN Copper
  • 10 AWG THWN Copper

NEC Reference: NEC 430.248

Question 37: If the conduit is placed in hazardous locations, it must be made ...................... to prevent sparking when a fault current flows through it.

  • sealed
  • bonded
  • wrentchtight
  • rugged plastic

NEC Reference: NEC 500.8(E)

Question 38: A mechanical contractor wants to run a water supply pipe through the dedicated electrical space directly above a 200A panelboard. Is this permitted?

  • Yes — water pipe above the panel is fine as long as it does not drip
  • No — foreign systems including pipes are not permitted in the dedicated electrical space
  • Yes — but a drip shield must be installed above the panel
  • Yes — the pipe is permitted if it runs parallel to the panel, not over it

NEC Reference: NEC 110.26(F)(1)(b)

Question 39: If the replacement compressor motor draws 35 amperes current, what is the minimum rating for disconnecting means used to protect the motor?

  • 40.25 amperes
  • 42 amperes
  • 38.5 amperes
  • 43.75 amperes

NEC Reference: NEC 440.12(A)(1)

Question 40: Which of the following is the length of the 120 volt flexible cord that — supplies a room air-conditioner?

  • 10 ft
  • 6 ft
  • 8 ft
  • 9 ft

NEC Reference: NEC 440.64

Question 41: Which of the following is NOT a standard overcurrent device size listed in 240.6(A)?

  • 45A
  • 55A
  • 110A
  • 175A

NEC Reference: NEC 240.6(A)

Question 42: What is the minimum operating rating of short circuit ground fault protective device that can be used for individual motor-compressor?

  • 10 A
  • 15 A
  • 20 A
  • 25 A

NEC Reference: NEC 440.22(A)

Question 43: A 2/0 THWN conductor is placed in a dry location where the ambient temperature is 450C. What is corrected ampacity of the conductor?

  • 170 Amperes
  • 160 Amperes
  • 165 Amperes
  • 175 Amperes

NEC Reference: NEC 310.15(B)(16)

Question 44: The grounded conductor terminal shall terminate with in the panel board in an individual terminal.

  • True
  • False

NEC Reference: NEC 408.41

Question 45: The recreational park is having fifteen 20 A supply facilities, ten 20A and 30 A supply facilities and twenty five 50A supply facilities is operated at 120/240 V single phase. What is the service demand load for the recreational park?

  • 480 A
  • 533 A
  • 686 A
  • 564 A

NEC Reference: NEC 551.73(A)

Question 46: What is the minimum load of household Electric cloth dryer in a dwelling unit?

  • 5000 Volt-ampere
  • 1500 Volt-ampere
  • 3000 volt-ampere

NEC Reference: NEC 220.54

Question 47: The mobile home park which has 25 site facilities is fed from a 240 V service feeder. What is the demand load for mobile home park?

  • 400 A
  • 450 A
  • 500 A
  • 380 A

NEC Reference: NEC 550.31

Question 48: Which of the following is the minimum branch circuit size operated at 480 volts and with out any correction factors?

  • Continuous load plus non-continuous load
  • Continuous load plus 125 % of non-continuous load
  • 125% of Continuous load plus non-continuous load
  • 125% of Continuous load

NEC Reference: NEC 210.19(A)(1)

Question 49: What is the general lighting load (in volt-amperes per square foot) used for a single-family dwelling when doing a standard load calculation?

  • 1.5 VA/sq ft
  • 2 VA/sq ft
  • 3 VA/sq ft
  • 3.5 VA/sq ft

NEC Reference: NEC Table 220.12

Question 50: If a 20 ampere ac snap switch is used to disconnect a 1.5 Hp motor what must be the maximum full load current of a motor?

  • 16 Amperes
  • 20 Amperes
  • 15 Amperes
  • 17 Amperes

NEC Reference: NEC 430.109(c)(2)

Question 51: How many number of 500 kcmil THWN conductors that can be installed in a 4 in. * 4 in. wireway?

  • 4 conductors
  • 5 conductors
  • 6 conductors
  • 7 conductors

NEC Reference: NEC 376.22(A)

Question 52: The 30 amp branch circuit provided for laundry outlet shall not have any other outlet.

  • True
  • False

NEC Reference: NEC 210.11

Question 53: The Transformer secondary is protected with GFCI which is connected to impedance heating elements. What is the maximum secondary voltage?

  • 30 volts
  • 80 volts
  • 50 volts
  • 60 volts

NEC Reference: NEC 424.32

Question 54: Type UF cable is rated for underground and wet locations. Can it also be used for interior branch circuit wiring inside a building?

  • No — Type UF is only approved for underground use
  • Yes — it can be used for interior branch circuits where NM cable is allowed
  • Yes — but only in wet or damp interior locations
  • No — Type UF requires conduit protection when installed indoors

NEC Reference: NEC 340.10(B)(4)

Question 55: A breaker is used to switch fluorescent lighting on and off many times a day. What special rating must this breaker have?

  • The breaker must be rated GFCI
  • The breaker must be rated SWD (switching duty) or HID
  • Any standard breaker is acceptable for lighting
  • The breaker must be rated for continuous operation

NEC Reference: NEC 240.83(D)

Question 56: The total connected load of dwelling unit is 11000 VA , what is the calculated demand load?

  • 3150 VA
  • 11000 VA
  • 9000 VA
  • 6000 VA

NEC Reference: NEC 240.42

Question 57: What is the maximum overall length of the power supply cord for mobile homes?

  • 36 1/2 feet
  • 21 feet
  • 28 1/2 feet
  • 20 feet

NEC Reference: NEC 550.10(D)

Question 58: The secondary systems of lighting circuits shall not be grounded.

  • True
  • False

NEC Reference: NEC 411.5

Question 59: 210.20(A) requires branch-circuit OCPD at not less than 125% of continuous load + 100% of non-continuous, except where:

  • The breaker and enclosure are listed for 100% continuous operation
  • The load is below 16A
  • The branch circuit is GFCI protected
  • No exception applies

NEC Reference: NEC 210.20(A) Exception

Question 60: Field installed secondary circuit winding for electrical signs of 1000 volts or less shall have a conductor size not less than .....................

  • 18 AWG
  • 16 AWG
  • 14 AWG
  • 12 AWG

NEC Reference: NEC 600.3

Question 61: What is the minimum size copper EGC for a circuit protected by a 200A overcurrent device?

  • 10 AWG copper
  • 8 AWG copper
  • 6 AWG copper
  • 4 AWG copper

NEC Reference: NEC Table 250.122

Question 62: The FMC cable shall be supported and secured at intervals less than ......................

  • less than 3 1/2 inches
  • less than 4 1/2 inches
  • less than 5 1/2 inches
  • less than 6 1/2 inches

NEC Reference: NEC 348.30(A)

Question 63: To qualify as a concrete-encased grounding electrode, a rebar or conductor encased in concrete must be at least how long?

  • 8 feet
  • 10 feet
  • 20 feet
  • 30 feet

NEC Reference: NEC 250.52(A)(3)

Question 64: Which of the following is the smallest size grounded electric conductor for an electric service using 1200 kcmil copper conductor?

  • 2/0 copper
  • 3/0 copper
  • 1/0 copper
  • 4 AWG copper

NEC Reference: NEC 250.66

Question 65: The interior metal water piping system must be bonded to the electrical service. Where must this bond be made, and what size conductor is required?

  • At any accessible point, sized by Table 310.16
  • At or near the service, sized by Table 250.102(C)(1) based on service conductor size
  • At every metal fixture, using 14 AWG minimum
  • Only at the water heater, using 6 AWG minimum

NEC Reference: NEC 250.104(A)

Question 66: What is the smallest rating plug fuse that is used for residential 120 volts branch circuit?

  • 15 amperes
  • 20 amperes
  • 12 amperes
  • 18 amperes

NEC Reference: NEC 240.6(A)

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
WHY GO PRO

Every Maryland Variant. One Real Result.

You just practiced on one full-length, Maryland-style exam built to mirror the real licensing test — timing, weighting, and difficulty included.

Up to 15 Maryland ExamsEvery test variant, one purchase
Detailed ReportsEvery attempt, topic-by-topic
Study CoachA personalized plan that adapts to you

One-time payment — $19.00, lifetime access to Maryland

Unlock Pro
EXAM CARD JOURNEYMAN FULL-LENGTH PRO
Questions66
Time limit240 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)
About This Exam

Sized and paced to match a real state licensing exam (Maryland). Finish it to get a free category-by-category score report.


Go Pro
  • Up to 15 Maryland exam variants
  • Detailed topic report every time
  • Personalized study guides & Study Coach

One-time payment — $19.00, lifetime access

See Pro Plans